| Calculating Your Ventilation Requirements | ||
| Example: Calculating the number of lineal feet of Cobra® Exhaust Vent needed for a 30x 40 attic: | ||
| Step 1 | Calculate attic square footage
How: Multiply length of attic (in feet) times width of attic (in feet) 30 x 40 = 1,200 square feet |
Intake ventilation MUST be at least equal to exhaust
ventilation.
Remember:
|
| Step 2 | Calculate NFA (Net Free Area) needed for
this attic by using the 1 in 300 rule How: Divide attic square footage by 300 1,200 sq. ft. ÷ 300 = 4 square feet of NFA needed |
|
| Step 3 | Convert square feet of NFA to square inches
How: Multiply square feet of NFA by 144 4 sq. ft. x 144 = 576 square inches of NFA needed |
|
| Step 4 | Split the amount of NFA needed equally between the intake and the exhaust How: Divide square inches of NFA needed by 2 576 sq. in. ÷ 2 = 288 square inches of NFA needed equally for exhaust & intake |
|
| Step 5 | Calculate # of lineal feet of Cobra®
Exhaust Vent
How: Divide the square inches of NFA needed at the ridge by the NFA of the Cobra® Exhaust Vent (Cobra® Exhaust Vent has 16.9 sq. inches of NFA per lineal foot) 288 sq. in. ÷ 16.9 = 17 lineal feet This attic requires 17 lineal feet of Cobra® Exhaust Vent to meet FHA minimum requirement |
|