Cobra Exhaust Vent Product Information |
Cobra Exhaust Vent Instructions, Data Sheets, Codes |
Cobra® Exhaust Vent for Roof Ridge
Effective attic ventilation is critical
for a long-lasting roof!
Cobra® exhaust vent is a key part of the GAF-Elk Smart Choice® Roof System Solution, and has even earned the prestigious Good Housekeeping Seal.
Homeowner’s Best Choice
*Under controlled laboratory conditions **See ltd. warranty for complete coverage and restrictions |
Professional’s Best Choice
Florida Building Code ICC-ES-ESR 1265 |
Balanced Ventilation Requirements
Balanced ventilation requires an equal amount of intake ventilation and exhaust ventilation. GAF-Elk recommends, at a minimum, providing 1 square foot of Net Free Ventilation for every 300 square feet of attic floor space. Consult local building codes for specific ventilation requirements in your area.
- Calculate the total square footage of the attic floor area (round up to the next highest number). This number will determine the minimum total linear feet of Cobra® exhaust vent that is needed.
- Find the appropriate amount of Cobra® exhaust vent and minimum intake ventilation that corresponds to the total attic square footage.
|
Based on 1/300 Rule |
||
|
Total
Attic Square Footage |
Recommended Length of Cobra® Exhaust Vent (Feet)* |
Minimum Intake Ventilation (Net Free Area in Sq. In.)* |
|
1600 |
23/28 |
389/395 |
|
1900 |
27/33 |
457/466 |
|
2200 |
32/38 |
541/536 |
|
2500 |
36/43 |
609/607 |
|
2800 |
40/48 |
676/677 |
|
3100 |
45/53 |
761/748 |
|
3400 |
49/58 |
829/818 |
*First figure pertains to Hand Nail, second figure pertains to Nail Gun.
NOTE: Always have a balanced ventilation system. In no case should the amount of exhaust ventilation at the ridge exceed the amount of soffit ventilation.